Description
PFC2-80kVAR | 3-Phase 80kVAR Power Factor Correction Capacitor Switch | 415V
The PFC2-80kVAR is a robust 3-phase Power Factor Correction (PFC) capacitor switch designed to provide reliable and efficient switching of capacitive loads in industrial power factor correction systems. Using advanced two-leg (2/3rds) control technology, the PFC2 Series significantly reduces the high inrush currents associated with conventional contactor-based capacitor switching while eliminating contact wear and electrical arcing.
Designed for 80kVAR capacitor banks operating on 415V three-phase supplies, the PFC2-80kVAR utilises solid-state switching technology for rapid and repetitive operation without mechanical contacts. Controlled via an 8–24V DC signal, the controller incorporates automatic over-temperature protection, high-speed semiconductor fuse protection, integrated fan cooling, LED status indicators, and fault monitoring for dependable long-term performance.
Ideal for industrial environments where reactive power demand changes rapidly, the PFC2-80kVAR helps improve power factor, reduce reactive power charges, and increase overall electrical system efficiency.
Key Features
- 80kVAR three-phase capacitor switching
- Two-leg (2/3rds) control technology
- Designed for Power Factor Correction (PFC) systems
- Reduces capacitor inrush current
- Eliminates mechanical contact wear and arcing
- Fast solid-state switching for frequent operation
- Controlled switch-off minimises flicker and RFI
- 8–24V DC control input
- Automatic over-temperature protection with auto reset
- Integral high-speed semiconductor fuse protection
- Integrated cooling fan
- LED status and fault indicators
- Voltage-free alarm relay output
- Compact IP20 enclosure
- Suitable for capacitor banks with or without detuning chokes
Technical Specifications
Electrical
- Power rating: 80kVAR
- Current rating: 125A
- Supply voltage: 415V RMS ±10%
- Frequency: 50/60Hz
Control Input
- Control signal: 8–24V DC
- Compatible with:
- Common 0V
- Common +VE
- Open collector
- Volt-free contact
Alarm Relay
- Voltage-free relay contacts
- Rating: 125V AC @ 2A
LED Status Indicators
- Green: DC power ON
- Orange: Signal enabled
- Red: Fault indication
- Red/Orange: Capacitors discharging
Protection Features
Over-Temperature Protection
- Trip temperature: 90°C ±1°C
- Automatic reset: 85°C ±1°C
Phase Loss & Fuse Failure: Alternating red and orange LED indication
Sensor Loss Detection: Equal interval flashing LED
Fault Status: Continuous 1.5-second flashing indication
Cooling
- Integrated 24V DC cooling fan
- Fan switch-on temperature: Approximately 55°C
Cable Connections
Power
- Supply
- Load
- Earth
Terminal capacity: 35mm² rising clamp terminals
Recommended cable size: 80kVAR: 35mm²
Signal Connections
- Alarm relay: 2.5mm² rising clamp terminal
- Control signal: 2.5mm² rising clamp terminal
Terminal Torque: 3.2Nm min, 3.7Nm max (35mm²) Power terminals only.
Protection: IP20
Fuse Protection: 160EET (160A), High-Speed Semiconductor Fuse or equivalent
Environmental: Maximum operating temperature: 65°C
Mechanical
Dimensions: 270mm (D) x 250mm (W) x 130mm (H)
Mounting: 4 × 4.5mm keyhole fixing slots.
Fixing centres: 227mm × 200mm
Weight: 5.6kg
Applications
The PFC2-80kVAR is suitable for 3-wire, three-phase floating-star or closed-delta capacitive loads, including capacitor banks fitted with or without detuning chokes.
Typical applications include:
- Industrial Power Factor Correction systems
- Automatic capacitor banks
- Manufacturing facilities
- Welding plants
- Crane systems
- Lift installations
- Wind power generation
- Renewable energy systems
- Heavy industrial machinery
- Electrical distribution panels
- Commercial power management systems
Benefits
- Dramatically reduces capacitor inrush current
- Eliminates mechanical contact wear
- Enables rapid and repetitive capacitor switching
- Improves power factor correction efficiency
- Minimises electrical flicker and RFI
- Extends capacitor bank service life
- Improves electrical system reliability
- Reduces maintenance requirements
- Suitable for demanding industrial environments
Safety Information
Warning:
- Isolate the electrical supply before removing the cover.
- The enclosure and heatsink may become hot during operation.
- Do not obstruct or cover the ventilation openings.
- Installation should be carried out by suitably qualified personnel using appropriate electrical protection devices.