Description
The ServiceGuard System is an advanced gas proving and services isolation solution designed to meet the rigorous safety standards of IGEM/UP/11 Edition 2 for gas safety. This system is ideal for environments that require precise control over gas and electric supplies, offering enhanced safety and operational flexibility.
With a single key switch, the ServiceGuard allows you to enable the system and turn individual services—gas and electric—on or off according to your needs. The backlit LCD display provides clear, real-time status updates, including gas pressures, sensor levels, and any issues with external devices like ventilation systems.
The ServiceGuard is specifically engineered to isolate all services when a room is vacant, protecting the area from potential misuse or vandalism, making it perfect for educational establishments, laboratories, and other high-safety environments.
Key Features:
- Clear LCD Indication: Real-time updates and clear instructions ensure easy operation.
- No Commissioning Required: Simplifies installation for quick setup.
- Annual Service Reminder: Keeps the system maintained with timely service notifications.
- 24V DC Auxiliary Power Output: Powers connected devices such as gas and CO2 sensors.
- Versatile Interfaces: Integrates seamlessly with gas sensors, CO2 sensors, ventilation systems, and remote emergency stop buttons.
- Built-In Time Delays: Prevents nuisance tripping for reliable performance.
- 5-Year Warranty: Ensures long-term reliability and peace of mind.
- UK Manufactured: Built with precision and adherence to high-quality standards.
Technical Specifications:
- Power Supply: 100 – 250VAC 50/60Hz
- Power Consumption: 40W Max
- Power Output:
- Gas Solenoid: Switched Mains
- Electrical Contactor: Switched Mains
- IP Rating: IP65 (with rear entry sealed)
- Approval: CE, UKCA Certified
External Device Interfaces:
- Valve Status: SPST – 5A @ 250V Max
- Pressure Transmitter: Monitors proving transmitter.
- 24V Out: Auxiliary supply (300mA Max) for CO2T, FGS, and FCMON.
- Gas Sensor: BACnet Interface for seamless integration.
- CO2 Sensor: 24V signal to monitor external voltage-free contacts (VFC).
- Intake & Extract Fans: 24V signal for controlling ventilation systems.
- Remote Stop: 24V signal to monitor external VFC for emergency shutdown.
Installer Selectable Options:
- Gas Pipework Fill Time: 5 or 10 seconds options.
- Availability Timer: Options include Off, 4, 8, or 16 hours.
- Availability Time: Configurable for Gas and Electric services.
The ServiceGuard System provides a reliable, all-in-one solution for gas proving and electric service isolation, ensuring maximum safety and control across a wide range of applications. Whether in a classroom, laboratory, or commercial space, the ServiceGuard System delivers top-tier performance and security.